Badi, Manjulata (2012) Power quality improvement using passive shunt filter, TCR and TSC combination. MTech thesis.
PDF 1110Kb |
Abstract
Power system harmonics are a menace to electric power systems with disastrous consequences. The line current harmonics cause increase in losses, instability, and also voltage distortion. With the proliferation of the power electronics converters and increased use of magnetic, power lines have become highly polluted. Both passive and active filters have been used near harmonic producing loads or at the point of common coupling to block current harmonics. Shunt filters still dominate the harmonic compensation at medium/high voltage level, whereas active filters have
been proclaimed for low/medium voltage ratings. With diverse applications involving reactive power together with harmonic compensation, passive filters are found suitable [41]. Passive filtering has been preferred for harmonic compensation in distribution systems due to low cost,
simplicity, reliability, and control less operation [42].
The uncontrolled ac-dc converter suffers from operating problems of poor power factor, injection of harmonics into the ac mains, variations in dc link voltage of input ac supply, equipment overheating due to harmonic current absorption, voltage distortion due to the voltage drop caused by harmonic currents flowing through system impedances, interference on telephone and communication line etc. The circuit topologies such as passive filters, ac-dc converter, based improved power quality ac-dc converters are designed, modeled and implemented. The main emphasis of this investigation has been on a compactness of configurations, simplicity in control, reduction in rating of components, thus finally leading to saving in overall cost. Based on thesis considerations, a wide range of configurations of power quality mitigators are developed, which is expected to provide detailed exposure to design engineers to choose a particular configuration for a specific application under the given constraints of economy and desired performance. For bidirectional power flow applications, the current source converter is designed and simulated with R-L load.
The necessary modeling and simulations are carried out in MATLAB environment using SIMULINK and power system block set toolboxes. The behavior of different configurations of
passive tuned filters on power quality is studied. One of the way out to resolve the issue of reactive power would be using filters and TCR, TSC with combination in the power system.
Installing a filter for nonlinear loads connected in power system would help in reducing the harmonic effect. The filters are widely used for reduction of harmonics. With the increase of nonlinear loads in the power system, more and more filters are required. The combinations of passive filters with TCR and TSC are also designed and analyzed to improve the power quality at ac mains. This scheme has resulted in improved power quality with overall reduced rating of passive components used in front end ac-dc converters with R-L load.
Item Type: | Thesis (MTech) |
---|---|
Uncontrolled Keywords: | Passive filter, TCR, TSC, P-I controller |
Subjects: | Engineering and Technology > Electrical Engineering > Power Electronics |
Divisions: | Engineering and Technology > Department of Electrical Engineering |
ID Code: | 3990 |
Deposited By: | BADI MANJULATA |
Deposited On: | 08 Jun 2012 10:29 |
Last Modified: | 08 Jun 2012 10:29 |
Supervisor(s): | Mohanty, K B |